The Type LB Conduit Body is used for a change of direction of the conduit run with the back hub usually exiting through a wall. It is a rectangular shaped conduit body with a removable cover and a foam gasket that is provided. It will have one entrance hub at one end and one hub at the opposite end in the back (floor).
Product Width (in.): 5.1 in
Product Width (in.) | 5.1 in |
---|
Conduit Compatibility | PVC | Material | PVC |
---|---|---|---|
Pack Size | 1 | Product Weight (lb.) | 4.362 lb |
Returnable | 90-Day |
Certifications and Listings | UL Listed | Manufacturer Warranty | Limited 1 year |
---|
3 Wire fill is XHHW #4/0 per UL Listing with a volume of 63.5 CU. IN. Max. fill must be under that total, refer to NEC 70, 314.28 for radius bending.
The color is grey.
Yes. All of our Schedule 40 and Schedule 80 products are ETL Listed and conform to UL 651 standard “Sunlight Resistant” specifications.
Under product details it states "for indoor use only". For this reason alone I have been sourcing other conduit bodies rather than buy from Home Depot as I'm sure many others have as well. I would urge you to contact H.D. to get this changed.
Our 3 wire fill is XHHW #4/0 for the 2” LB. A 4/0 XHHW has a cross sectional area of 0.3197 sq. inches. 3 conductors is a total of 0.9591 sq. inches. You’ll need to calculate the area of the wires you’re using to make sure you’re under the 3 wire fill.
Depends on the size of the wire. I am having difficulty bending 4/0 aluminum wires to get through the body. It can be done, but I don't know the tricks.
Was able to physically pull 2 x 4/0 and 1 x 3/0 aluminum wire, 1 x UF-B 10-2 and 1 x UF-B 12-2 copper wires. Getting a grip on the 4/0 cable was the key factor with some wire pulling lube. My medium sided bench top vise was a good tool to pull
Yes this can be used for that.
Horizontally, the distance from connector edge to center of 90 connector is 8.128”.
We have stock in our plant; please reach out to your local store or DC for product availability in store.
Yes they are; they are even rate for 3-wire fill for XHHW #4/0
Viewing 1-8 of 20